Shenzhen CODT technology co.,Ltd

Create Our Dreams Together

Manufacturer from China
Active Member
3 Years
Home / Products / Cable Gland Explosion Proof /

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

Contact Now
Shenzhen CODT technology co.,Ltd
City:shenzhen
Country/Region:china
Contact Person:Anne
Contact Now

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

Ask Latest Price
Video Channel
Brand Name :CODT
Model Number :gland
Certification :IECEx,ATEX
Place of Origin :CHINA
MOQ :negotiable
Price :negotiable
Payment Terms :T/T, L/C
Supply Ability :500 pcs per day
Delivery Time :5-20days
Packaging Details :carton box standard, check the specification
ITEM TYPE :GLAND
IP :IP66
WARRANTY :5 YEARS
CERTIFICATION :ATEX,IECEX
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Buy Now M20*1.5 Explosion Proof Cable Glands Exproof Unarmoured for Hazardous Areas Ex d Metal Non-armoured Zone 1 2 21

  • EX-QM01-A1

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Single seal, suitable for unarmored cable.

Ex e, structure.

Degree of protection: IP66/IP68.

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Marking ATEX

Ex eb ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperature:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread AG(mm) Overall Cable Diameter ΦB(mm) Minimum Thread Length GL(mm) Nominal Protrusion
Length L(mm)
Across Flats/Corner S(ΦE) (mm)
Metric NPT Min Max
16 M16*1.5 NPT3/8 9.5 12 16 30 27(29)
20 M20*1.5 NPT1/2 9.5 16.5 16 30 27(29)
25 M25*1.5 NPT3/4 14 20 16 38 34(37)
32 M32*1.5 NPT1 18 26 18 44 40(44)
40 M40*1.5 NPT1 1/4 24 32.5 18 46 50(55)
50 M50*1.5 NPT1 1/2 30 41 20 50 60(67)
63 M63*1.5 NPT2 40 52 21 64 68(73)
75 M75*1.5 NPT2 1/2 50 65 22 70 86(89)
90 M90*1.5 NPT3 62 77 22 80 102(105)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM03-C1K

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Single seal, suitable for armored cable.

Valid over the entire temperature range from -50°C to 80°C (-58 ºF to 176ºF)

Degree of protection: IP66/IP68

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb

Ex db ⅡC Gb Ex tb ⅢC Db IP66/IP68

Marking IECEx

Ex eb ⅡC Gb

Ex db ⅡC Gb Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread AG(mm) Overall Cable Diameter Minimum Thread Length GL(mm) Nominal Protrusion
Length L(mm)
Across Flats/Corner S(ΦE) (mm)
ΦB(mm) ΦC(mm)
Metric NPT Min Max Max
16 M16*1.5 NPT3/8 9.5 12 / 16 65 24(29)
20 M20*1.5 NPT1/2 9.5 16.5 / 16 67 30(34)
25 M25*1.5 NPT3/4 14 20 / 16 71 36(40)
32 M32*1.5 NPT1 18 26 / 18 76 45(51)
40 M40*1.5 NPT1 1/4 24 32.5 / 18 76 55(61)
50 M50*1.5 NPT1 1/2 30 41 / 20 91 68(74)
63 M63*1.5 NPT2 40 52 / 21 98 86(95)
75 M75*1.5 NPT2 1/2 50 65 / 22 102 95(109)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM04-B1K

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Dual seal, suitable for armored cable.

Valid over the entire temperature range from -50°C to 80°C (-58 ºF to 176ºF)

Degree of protection: IP66/IP68.

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Marking IECEx

Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread AG(mm) Overall Cable Diameter Minimum Thread Length GL(mm) Nominal Protrusion
Length L(mm)
Across Flats/Corner S(ΦE) (mm)
ΦB(mm) ΦC(mm)
Metric NPT Min Max Min Max
16 M16*1.5 NPT3/8 9.5 12 6.5 10.5 16 65 24(29)
20 M20*1.5 NPT1/2 9.5 16.5 10 14.5 16 67 30(34)
25 M25*1.5 NPT3/4 14 20 12.5 19.5 16 71 36(40)
32 M32*1.5 NPT1 18 26 19 25.5 18 76 45(51)
40 M40*1.5 NPT1 1/4 24 32.5 25 31 18 76 55(61)
50 M50*1.5 NPT1 1/2 30 41 31.5 43 20 91 68(74)
63 M63*1.5 NPT2 40 52 42.5 50 21 98 86(95)
75 M75*1.5 NPT2 1/2 50 65 54.5 65 22 102 95(109)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM05-C1K

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Single seal, suitable for armored cable.

Valid over the entire temperature range from -50°C to 80°C (-58 ºF to 176ºF)

Degree of protection: IP66/IP68.

  • APPLICATION

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Marking IECEx

Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread AG(mm) Overall Cable Diameter Minimum Thread Length L1(mm) Total Length l(mm) Across Flats/Corner S(ΦE) (mm)
ΦB(mm) ΦC(mm)
Metric NPT Min Max Max
16 M16*1.5 NPT3/8 7 16 8 15 85 24(27)
20 M20*1.5 NPT1/2 7 16 10.5 15 87 24(27)
25 M25*1.5 NPT3/4 14 20 15 15 88 30(33)
32 M32*1.5 NPT1 18 25 20 17 96 36(39)
40 M40*1.5 NPT1 1/4 24 33 27 19 105 45(50)
50 M50*1.5 NPT1 1/2 31 40 31 19 108 55(60)
63 M63*1.5 NPT2 41 50 41 20 118 68(73)
75 M75*1.5 NPT2 1/2 52 63 55 21 124 86(89)
90 M90*1.5 NPT3 65 76 65 24 128 96(99)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM06-B1K

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Dual seal, suitable for armored cable.

Valid over the entire temperature range from -50°C to 80°C (-58 ºF to 176ºF)

Degree of protection: IP66/IP68.

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb/Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Marking ATEx

Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread (mm) Overall Cable Diameter Minimum Thread Length L1(mm) Total Length L(mm) Across Flats/Corner S(ΦE) (mm)
ΦB(mm) ΦC(mm)
Metric NPT Min Max Min Max
16 M16*1.5 NPT3/8 7 16 5 8 15 85 24(27)
20 M20*1.5 NPT1/2 7 16 5 10.5 15 87 24(27)
25 M25*1.5 NPT3/4 14 20 8 15 15 88 30(33)
32 M32*1.5 NPT1 18 25 11 20 17 96 36(39)
40 M40*1.5 NPT1 1/4 24 33 14 27 19 105 45(50)
50 M50*1.5 NPT1 1/2 31 40 20 31 19 108 55(60)
63 M63*1.5 NPT2 41 50 30 41 20 118 68(73)
75 M75*1.5 NPT2 1/2 52 63 42 55 21 124 86(89)
90 M90*1.5 NPT3 65 76 52 65 24 128 96(99)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM10-B1

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Single seal, suitable for unarmored cable

Ex d structure.

Degree of protection: IP66/IP68.

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb/ Ex db IIC Gb

Ex tb ⅢC Db IP66/IP68

Marking ATEx

Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread (mm) Overall Cable Diameter ΦB(mm) Minimum Thread Length L1(mm) Total Length L(mm) Across Flats/Corner S(ΦE) (mm)
Metric NPT Min Max
16 M16*1.5 NPT3/8 4 7 16 62 27(29)
20 M20*1.5 NPT1/2 5 8 16 62 27(29)
25 M25*1.5 NPT3/4 8 12 16 62 30(33)
32 M32*1.5 NPT1 12 16 18 67 38(42)
40 M40*1.5 NPT1 1/4 16 24 20 77 45(50)
50 M50*1.5 NPT1 1/2 18 28 20 79 55(60)
63 M63*1.5 NPT2 25.5 38 20 81 68(73)
75 M75*1.5 NPT2 1/2 29 46 20 100 85(89)
90 M90*1.5 NPT3 41 60 21 100 98(102)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM10-B1

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Single seal, suitable for unarmored cable

Ex d structure.

Degree of protection: IP66/IP68.

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb/ Ex db IIC Gb

Ex tb ⅢC Db IP66/IP68

Marking ATEx

Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread (mm) Overall Cable Diameter ΦB(mm) Minimum Thread Length L1(mm) Nominal Protrusion Length(mm) Across Flats/Corner S(ΦE) (mm)
Metric NPT Min Max
16 M16*1.5 / 5 8 15 30 24(27)
20 M20*1.5 NPT1/2 7.5 11.5 15 30 24(27)
25 M25*1.5 NPT3/4 11 14.5 15 30 30(33)
32 M32*1.5 NPT1 14 20 20 32 36(39)
40 M40*1.5 NPT1 1/4 19 20 20 32 45(50)
50 M50*1.5 NPT1 1/2 25 32 20 36 55(60)
63 M63*1.5 NPT2 31.5 42.5 20 37 68(73)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM13-B1T

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Single seal, suitable for unarmored cable

Ex d structure.

Degree of protection: IP66/IP68.

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb/ Ex db IIC Gb

Ex tb ⅢC Db IP66/IP68

Marking ATEx

Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread (mm) Overall Cable Diameter ΦB(mm) Minimum Thread Length L1(mm) Nominal Protrusion Length(mm) Across Flats/Corner S(ΦE) (mm)
Metric NPT Min Max
16 M16*1.5 / 5 8 15 40 24(27)
20 M20*1.5 NPT1/2 7.5 11.5 15 40 24(27)
25 M25*1.5 NPT3/4 11 14.5 15 40 30(33)
32 M32*1.5 NPT1 14 20 20 44 36(39)
40 M40*1.5 NPT1 1/4 19 20 20 48 45(50)
50 M50*1.5 NPT1 1/2 25 32 20 49 55(60)
63 M63*1.5 NPT2 31.5 43.5 20 63 68(73)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM18-C1

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Single seal, suitable for unarmored cable

Ex d structure.

Degree of protection: IP66/IP68.

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb/ Ex db IIC Gb

Ex tb ⅢC Db IP66/IP68

Marking ATEx

Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread (mm) Overall Cable Diameter ΦB(mm) Minimum Thread Length L1(mm) Nominal Protrusion Length(mm) Across Flats/Corner S(ΦE) (mm)
Metric NPT Min Max
16 M16*1.5 / 5 8 15 57 24(27)
20 M20*1.5 NPT1/2 5 8 15 57 24(27)
20 M20*1.5 NPT1/2 7.5 11.5 15 57 24(27)
25 M25*1.5 NPT3/4 11 14.5 15 57 30(33)
32 M32*1.5 NPT1 14 20 20 59 36(39)
40 M40*1.5 NPT1 1/4 19 26 20 60 45(50)
50 M50*1.5 NPT1 1/2 25 32 20 62 55(60)
63 M63*1.5 NPT2 31.5 43.5 20 73 68(73)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM21-C1K

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Single seal, suitable for unarmored cable.

Valid over the entire temperature range from -50°C to 80°C (-58 ºF to 176ºF)

Degree of protection: IP66/IP68.

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb/Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Marking ATEx

Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread (mm) Overall Cable Diameter Minimun Thread Length L1(mm) Total Length L(mm) Across Flats/Corner S(ΦE) (mm)
ΦB(mm) ΦC(mm)
Metric NPT Min Max Max
16 M16*1.5 NPT3/8 9.5 12 7 16 66 27(29)
20 M20*1.5 NPT1/2 9.5 16.5 12 16 66 27(29)
25 M25*1.5 NPT3/4 14 20 17 16 68 34(37)
32 M32*1.5 NPT1 18 26 23 18 77 40(44)
40 M40*1.5 NPT1 1/4 24 32.5 30 18 81 50(55)
50 M50*1.5 NPT1 1/2 30 41 37 20 88 60(67)
63 M63*1.5 NPT2 40 52 52 21 96 68(73)
75 M75*1.5 NPT2 1/2 50 65 62 22 114 86(89)
90 M90*1.5 NPT3 62 77 66 22 119 102(105)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • EX-QM22-B1K

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FEATURES

ATEX and IECEx certified for safe use in potentially explosive atmospheres

Dual seal, suitable for armored cable.

Valid over the entire temperature range from -50°C to 80°C (-58 ºF to 176ºF)

Degree of protection: IP66/IP68.

  • APPLICATION

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • TECHNICAL DATA

Marking ATEX

Ⅱ2 GD Ex eb ⅡC Gb/Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Marking ATEx

Ex eb ⅡC Gb/ Ex db ⅡC Gb

Ex tb ⅢC Db IP66/IP68

Standards

EN60079-0, EN60079-1, EN60079-7, EN60079-31, IEC 60079-0, IEC60079-1, IEC60079-7, IEC60079-31

Ambient Temperarture:-50℃ ≦ Tamb ≦ +80℃

Connection Thread:Metric Thread, NPT Thread

  • SELECTION TABLE OF CABLE GLAND
Gland Size Available Entry Thread (mm) Overall Cable Diameter Minimun Thread Length L1(mm) Total Length L(mm) Across Flats/Corner S(ΦE) (mm)
ΦB(mm) ΦC(mm)
Metric NPT Min Max Min Max
16 M16*1.5 NPT3/8 9.5 12 5 8 15 66 27(29)
20 M20*1.5 NPT1/2 9.5 16.5 8 10.5 15 66 27(29)
25 M25*1.5 NPT3/4 14 20 10 15 15 68 34(37)
32 M32*1.5 NPT1 18 26 15 19.5 19 77 40(44)
40 M40*1.5 NPT1 1/4 24 32.5 19 26 19 81 50(55)
50 M50*1.5 NPT1 1/2 30 41 26 32 19 88 60(67)
63 M63*1.5 NPT2 40 52 31.5 40 19 96 68(73)
75 M75*1.5 NPT2 1/2 50 65 38 50 19 114 86(89)
90 M90*1.5 NPT3 62 77 54.5 62 19 119 102(105)
  • SCHEMATIC DIAGRAM

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • ORDERING GUIDE

ATEX IP66 Cable Gland Explosion Proof Ex Proof Cable Gland IECEx

  • FAQ

    Q1. Can I have a sample order ?

    Yes, we welcome sample order to test and check quality. Mixed samples are acceptable.
    Q2: Do you offer guarantee for the products?
    Yes, we offer 2-5 years warranty to our products.

Inquiry Cart 0